Basement Dryer Exhaust Overhaul
& Smart Booster Telemetry

I tore out a lint-choked basement dryer run, rebuilt it in 4-inch rigid steel, hung a Tjernlund LB2 booster from an angle-iron bracket I made for the joist, and wired its run state into UniFi Protect. Here's what worked, what surprised me, and the spec I should have read first.

By Rick Breidenstein (VirtualRick) Published Nov 8, 2026 Updated Nov 21, 2026

TL;DR: What I Learned

  • The rigid pipe did most of the work. As soon as the old ducting was swapped for sealed, smooth 4-inch rigid steel, the LG dryer's own blower pushed all four exterior louvers wide open and blew out a pile of old lint, with the booster still in standby.
  • My run is too short for the LB2. Tjernlund's instructions (P/N 8505034) assume more than 25 equivalent feet. Mine is about 17 equivalent feet, so on a clean run the LB2's pressure sensing short-cycles. If your run is short too, fix the duct first and you may not need a booster at all.
  • Monitoring without touching the safety indicator. A Functional Devices RIBXGTF current switch on the fan's hot conductor feeds a dry contact into a UniFi USL-Relay. That gives me run/idle history and short-cycle alerts in Protect, and the LB2's own UL 705 indicator panel stays untouched.

Overview & Starting Conditions

Our laundry is on the first floor. The dryer is a front-load LG that's more than 10 years old, and it exhausts straight down through the floor into an unfinished basement joist bay. From there the duct runs across the bay and out a 4-inch louvered wall hood. Loads were taking longer and longer, and when I finally opened the run up the reason was obvious: years of lint caught on the restrictive old ducting and on screw tips poking into the airstream.

I had four goals going in:

  1. Get rid of every avoidable restriction in the roughly 17-equivalent-foot run and clear out the old lint.
  2. Add a Tjernlund LB2 inline dryer booster, mounted so its motor hum doesn't travel up through the floor.
  3. Keep the LB2's code-required local blockage indicator.
  4. Get the booster's run state into my existing UniFi Protect setup, so I can see runtime and catch problems from my phone.

This is a log of what I actually did. It isn't a universal installation manual. Your dryer's manual, the booster's manual and your local code come first. Where my build doesn't match the manufacturer's assumptions, I say so.

Project at a Glance

Appliance
LG front-load electric dryer, 10+ years old
Duct Route
1st-floor drop → basement joist bay → 4" louvered wall hood
Equivalent Length
~17 equivalent ft (4" rigid)
Booster
Tjernlund LB2: 160 CFM, 50 W / 0.5 A @ 120 VAC
Mount
Everbilt slotted angle iron + 6" fan bracket, 1/4"-20 nylock hardware
Telemetry
RIBXGTF current switch → USL-Relay I1 → Protect Alarm Manager

Bill of Materials

These are the parts I actually used, along with why I picked each one. The links are affiliate links. They don't change your price, and they help pay for the next project.

Part Why I Chose It Link
Tjernlund LB2 Dryer Duct Booster 160 CFM, 50 W / 0.5 A at 120 V. Microprocessor control with static-pressure and thermistor sensing, plus a remote 3-wire LED status panel. UL 705 listed. Amazon
4" rigid galvanized steel duct + rigid 90° elbows Smooth walls and the least friction loss. Every joint is nested male-into-female in the direction of airflow. Amazon
Nashua 367-17 foil HVAC tape UL 181A-P / 181B-FX listed. I sealed every seam with tape only, so there are no screws in the airstream. Amazon
Everbilt slotted steel angle iron Cut to length and bolted across the joist bay. The slots made it easy to fine-tune the fan's height and keep it lined up with the duct. Home Depot
6" galvanized fan bracket, 1/4"-20 hex bolts, nylon-insert locknuts Nylock nuts won't vibrate loose under constant motor hum. Drilled with 5/32" and 3/16" bits. Amazon
Functional Devices RIBXGTF (or RIBXKTF) Split-core AC current switch with a fixed 0.35 A trip point and an isolated N.O. output (0.4 A @ 30 V max). The solid-core RIBXKTF trips at 0.25 A. Amazon
Ubiquiti UniFi SuperLink Gateway + USL-Relay Two dry-contact inputs (I1/I2 to GND) that show up natively in UniFi Protect Alarm Manager. No Home Assistant bridge required. store.ui.com

Build Log

1

Fabricating the Angle-Iron Joist Bracket

Screwing the LB2 straight into a joist is the quickest way to turn the floor above into a speaker. Instead, I cut Everbilt slotted angle iron to span the joist bay and bolted a 6-inch galvanized fan bracket to it, so the booster hangs below the joists as a rigid drop mount.

  • All the hardware is 1/4"-20 hex bolts with nylon-insert locknuts. Regular nuts walk loose under a motor that runs for an hour at a time.
  • I opened up the holes in the bracket and the wood with 5/32" and 3/16" bits so the bolts went in straight without splitting the joist.
  • The slots in the angle iron let me raise or lower the fan in small steps until its collars lined up exactly with the duct. That matters because any offset becomes another restriction.
2

Rigid Duct Assembly, Nested With the Airflow

I tore out the old ducting completely and replaced it with smooth 4-inch rigid galvanized steel pipe and rigid 90° elbows. Two rules governed every joint:

  • The male end points downstream. Each crimped end slides into the next piece in the direction of airflow, so lint passes over a smooth lip instead of hitting an edge.
  • No sheet-metal screws. Screw tips inside a dryer duct act like hooks that collect lint. Every seam is sealed only with Nashua 367-17 UL 181A-P foil tape.

Field Hack: The Foil-Tape Peel Tab

Peeling the blue paper backing off foil tape with your fingernails while you're on a ladder in an overhead joist bay is miserable. Before tearing off a strip, I lightly score the backing about 1 inch from the end with a razor blade, without cutting the foil. That gives you a starter tab: bend it and the liner pops free. This one trick saved me more time than anything else on the project.

3

Wiring the Remote Status Panel

The LB2 comes with a remote LED indicator panel on a 3-conductor low-voltage harness (Red, White, Green). It's how the booster tells you it's running or that it has detected a blockage, and it's part of what makes the installation code-compliant. I wired it exactly as the manual shows and mounted it where we actually see it, rather than hiding it in the joists.

I left this panel's wiring completely alone when I added remote monitoring. More on why in the telemetry section.

4

Exterior Hood Cleanup

I cleaned the lint and cobwebs out of the hinges on the louvered wall hood until all four flaps swung freely and dropped fully shut when the dryer stopped. This turned out to matter for the booster's sensing too (see Findings): a flap that hangs open lets wind pressure into the pipe.

Do You Even Need a Booster? Equivalent-Length Check

4-inch smooth rigid duct: straight pipe 1:1, each 90° elbow = 5 ft, each 45° elbow = 2.5 ft (the same equivalents Tjernlund publishes for the LB2). Defaults match my run.

7 ft

Tape-measure distance of straight pipe

2

Smooth rigid 4" elbows

0

Offsets and gentle transitions

Total Equivalent Duct Run
17 Equivalent Feet

The IRC's default maximum for dryer exhaust is 35 equivalent ft unless your dryer manufacturer's instructions allow more. Many manufacturers do allow longer runs for rigid duct, so check your dryer's manual. This calculator is a planning aid, not a code determination.

Engineering & Diagnostic Findings

1. The rigid pipe alone restored the airflow

The first test run after the rebuild surprised me. With the LB2 still in standby, the LG's internal blower pushed all four louvers on the exterior hood wide open and blew a large clump of old lint out of the hood. That lint had been building up there for years. Smooth, sealed, correctly nested rigid pipe got rid of enough resistance that the dryer could clear its own exhaust again.

2. Why the LB2 short-cycles on my short, clean run

After the rebuild, the LB2 would occasionally drop into its transition state and cycle off and on mid-load, without throwing a red blockage fault. Re-reading the installation instructions (P/N 8505034) explained it:

  • The LB2 is meant for runs of more than 25 equivalent feet. Tjernlund says not to install it on shorter runs.
  • Without a secondary lint trap, it wants at least 15 equivalent feet of duct upstream of the fan, plus about 24 inches of straight pipe ahead of the intake collar.
  • My joist bay is tight, so a 90° elbow feeds almost directly into the LB2's intake, and the whole run is only about 17 equivalent feet.

Clean rigid pipe produces very little static back-pressure. Add the turbulence of an elbow right at the intake, and the LB2's 160 CFM blower can briefly pull a low-pressure eddy across its internal sensing port. The controller reads that as "the dryer stopped" and backs off, then sees pressure again and restarts. Honest bottom line: my installation doesn't meet the LB2's minimum-length requirement, and the short-cycling is the result. If your run is under about 25 equivalent feet, rebuild it in rigid pipe first and measure before buying a booster.

3. LG Sensor Dry vs. Manual Dry changes what the booster sees

The dryer cycle matters too. LG's Sensor Dry programs (Cotton/Normal) adjust heat and airflow, including the Flow Sense duct check at startup. That produces exactly the kind of uneven pressure a pressure-sensing booster has trouble following. Manual Dry (Speed Dry, High heat) delivers flat, constant airflow, and in my tests the LB2 stayed on much more consistently during manual cycles. If you're diagnosing a booster that cycles, run one manual cycle before you blame the hardware.

4. Exterior louvers affect the pressure sensor

If the hood flaps don't close fully when the dryer stops, outside wind can push pressure back into the duct and confuse a differential-pressure sensor. That can cause phantom starts or a slow shutdown. Cleaning the hinges until the flaps dropped shut on their own fixed this for me. I now check the hood twice a year.

What I Observed Likely Cause What I Did / Recommend
LB2 cycles off/on mid-load, no red fault Run shorter than 25 eq. ft, elbow directly at the intake, low static pressure Add straight pipe ahead of the intake if there's room. Otherwise accept it, or skip the booster on short runs
Cycling worse on Sensor Dry than Manual Dry LG Flow Sense / modulated airflow during startup Compare against a Manual Dry (Speed Dry, High) cycle before troubleshooting the fan
Louvers barely opening before the rebuild Restrictive ducting, internal screw tips, lint buildup Smooth rigid pipe, joints nested with the airflow, foil tape only
Phantom starts on windy days Hood flaps not closing, so wind pressure gets into the duct Clean the hood hinges and confirm the flaps drop fully shut

UniFi Protect Remote Monitoring Architecture

The house already runs on UniFi Protect, so I wanted the booster's state in the same app as the cameras. I didn't want another hub or a cloud integration that might break with the next firmware update.

Why I didn't wire the LB2's LED panel into the relay

It's tempting to tap the 3-wire indicator harness, but it won't work and you shouldn't do it. The harness actively drives low-voltage LEDs. It doesn't switch dry contacts. The USL-Relay inputs (I1/I2) expect a passive dry-contact closure to GND. And the local blockage indicator is part of the booster's UL 705 safety function, so you shouldn't splice into it.

My approach: sense the motor current instead

A Functional Devices RIBXGTF split-core current switch clamps around the hot conductor only feeding the LB2. When the 0.5 A motor spins up, the current rises above the RIBXGTF's fixed 0.35 A trip point and its isolated N.O. output closes. That output goes to the USL-Relay's I1/GND, and Protect Alarm Manager sees a clean run/idle state change.

Tjernlund LB2
120 VAC, ~0.5 A when running
RIBXGTF Current Switch
On the hot leg only → N.O. closes > 0.35 A
USL-Relay
Input I1 / GND via SuperLink Gateway
Protect Alarm Manager
Run/idle history + push alerts

Alarm Manager Ideas

  • Runtime log: every I1 close/open is a timestamped booster run, which makes it easy to spot cycles that are getting longer as lint builds up.
  • Short-cycle alert: notify me if the input toggles repeatedly within a few minutes, which is the behavior described in Finding #2.
  • Stuck-on alert: notify me if the booster stays on far longer than a normal cycle.

Gotchas & Safety

  • Hot leg only. Clamping around a whole power cord (hot and neutral together) cancels the magnetic field, and the switch will never trip.
  • Thin margin. 0.5 A against a 0.35 A trip point isn't much headroom. Looping the hot conductor through the aperture twice doubles the sensed current. The RIBXKTF (0.25 A) is the other option.
  • Mains voltage. Separating the hot conductor means working inside a de-energized junction box. If you're not comfortable with that, hire an electrician and follow NEC and local code.
  • The output is low-voltage only (0.4 A @ 30 V max). That's perfect for a USL-Relay input. Never use it to switch line voltage.

What I'd Do Differently

Measure first, buy second

I should have calculated the equivalent length after planning the rigid rebuild. At about 17 ft, the rebuild alone might have been enough.

Plan for straight pipe at the intake

If you install a booster, lay out the joist bay so there's about 24 inches of straight pipe ahead of the intake. Don't let an elbow feed straight into the collar.

Sketch the bay before cutting

I built a free duct & joist sketcher after this project so I can lay out offsets, booster position and cut lists before touching the snips.

FAQ

Can I use a Tjernlund LB2 on a duct run shorter than 25 equivalent feet?

Tjernlund says not to. I did, and the result was the short-cycling described above. On a short run, smooth rigid duct and a clean hood usually fix the airflow without a booster.

Why not use screws on dryer duct joints?

Screw tips stick into the airstream and catch lint, which eventually builds into a blockage and a fire risk. Nest the joints with the airflow and seal them with UL 181A-P foil tape.

Can the LB2's indicator panel trigger a UniFi USL-Relay directly?

No. The panel harness drives LEDs and doesn't provide dry contacts, and you shouldn't modify the safety indicator anyway. A current switch on the fan's hot conductor gives you a clean, isolated contact instead.

My booster cycles on and off. Is it broken?

Probably not. First check that the run meets the minimum length, that there's straight pipe ahead of the intake, and that the hood flaps close fully. Then compare a Manual Dry cycle against Sensor Dry. If you get a red blockage fault, stop and inspect the duct.

⚡
Rick Breidenstein (VirtualRick)

I'm an IT guy who documents real projects from my own house: networking, UniFi Protect, and hands-on DIY like this duct rebuild. Everything here was bought, installed and lived with before I wrote about it. More about me · Questions or corrections?

Safety disclaimer: Dryer exhaust and line-voltage work carry real fire and shock risks. This page describes my own installation and isn't professional advice. Always follow your dryer and booster manufacturers' instructions, the IRC/NEC, and your local code, and hire a licensed professional when in doubt.